ONE (1) SITE VISIT/SITE WALK SHALL BE HELD AT LOCATION ON 21 MAY 2026 AT 1300 (1:00 PM).. **************************ALL CONTRACTORS SHALL HAVE: contractors MUST provide Real ID compliant documents (Real ID DL, Passport, Certificate of Naturalization, Birth Certificate, etc) to be granted access to the facility. The United States Coast Guard person to contact/ meet is CWO-2 CRITCHER. # 907-966-5500 justin.d.critcher@uscg.mil QUESTIONS AND ANSWERS TO FOLLOW HERE---- Questions asked besides the one you sent me: Request for clarification if there is any mechanical elements in the Secret space: No mechanical equipment in the Secret space, however there is one controller we are requesting replaced in that space. Request for clarification regarding access to the Secret space: Contractors accessing the secret space must pass a background check before being granted access. Please submit all documents at least 30 days prior to access date. Is there a damper in the Secret space? None that we are aware of Who is our usual controls contractor? Long Building Technologies Please provide the vetting criteria to allow an acceptable controller to be provided From our Security Staff: “any electronic/electrical device entering the secure space cannot transmit any signal of any kind wirelessly. This includes any controller permanently installed in the space.” SEE ATTACHED SCOPE OF WORK AND SPECIFICATIONS. - Replace Roof HVAC Units Air Station Sitka - PN 31098174. PR 51291PR260000059